Page 80
SECTION 4.2
OPERATIONAL ANALYSIS
PART 4
DC CONTROL
UTILITY VOLTAGE DROPOUT / ENGINE
CRANKING
• After fifteen (15) seconds and when the circuit
board's 15-second timer has timed out, if "Utility"
voltage is still below 60 percent of nominal, circuit
board action will energize the circuit board's crank
and run relays (K1 and K2) simultaneously.
• The crank relay (K1) will remain energized for about
15 seconds on the first crank cycle. The relay will
then de-energize for 7 seconds and will again
energize. This time it will remain energized for 7
seconds. Thus, the engine will crank cyclically for 7
second crank-rest cycles. This cyclic cranking will
continue until either the engine starts or until about
ninety (90) seconds of crank-rest cycles have
elapsed.
• When the crank relay (K1) is energized, circuit board
action delivers 12 volts DC to a starter contactor
relay (SCR), via Wire 56. When the SCR energizes,
its contacts close and battery power is delivered to a
starter contactor (SC). When the SC energizes, its
contacts close and battery power is delivered to the
starter motor (SM).The engine cranks.