Q What is the maintenance schedule?
A The maintenance schedule is in the owner’s
manual. The schedule varies between the air-
cooled and the liquid-cooled models.
Q What is the expected life of the engine?
A A properly maintained engine should provide over
20 years of operation under standby conditions.
Q How much oil does the engine crankcase hold?
A Air-cooled: (7 kW) = 1.5 qts
Air-cooled: (12 kW, 15 kW) = 1.7 qts
Liquid-cooled: 25 & 40 kW = 4.5 qts.
Q What type of oil is recommended?
A For air-cooled units: After the break in oil, an all
season synthetic oil 5W-30 should be used. API
Service Class SG, SH or SJ should be used in all
cases. The recommended oil for the liquid-cooled
units is 15W-40. All oils should be high detergent
oil that meets or exceeds API Service Class SG,
SH or SJ requirements for gasoline engines.
Q What is the required water column for
installation?
A Air-cooled generators require natural gas
pressure of 5” - 7” of water column (0.18 to 0.25
psi) or LP gas pressure of 11”-14” of water
column (0.4 to 0.5).
Liquid-cooled generators require natural gas
pressure of 5” - 14” of water column (0.18 to 0.5
psi) or LP gas pressure of 11”-14” of water
column (0.4 to 0.5).