TRANSFER SWITCH & Model ASPAS1BBA007 Model ASPAS1BBA012 Model ASPAS1BBA015
EMERGENCY LOAD CENTER (7kW) (12kW) (15kW)
No. of Poles 2 2 2
Current Rating (amps) ......................................................100 ..........................................100 ......................................... 100
Voltage Rating (VAC) ....................................................... 250 ......................................... 250 ......................................... 250
Utility Voltage Monitor (fixed)
-Pick-up ...........................................................................
70% ........................................ 70% ....................................... 70%
-Dropout .........................................................................
60% ....................................... 60% ....................................... 60%
Return to Utility ....................................................... approx. 13 sec .......................approx. 13 sec. ....................... approx. 13 sec.
Exerciser weekly for 12 minutes .................................. Standard .................................Standard .................................Standard
UL Listed ...................................................................... Standard .................................Standard .................................Standard
Dimensions (H” x W” x D”) .......................................26.5 x 12.5 x 7 ...................... 26.5 x 12.5 x 7 ....................... 26.5 x 12.5 x 7
Total of Pre-wired Circuits .................................................. 8 ............................................ 10 ...........................................12
No. 15A 120V .......................................................... 5 ............................................ 3 ........................................... 5
No. 20A 120V .......................................................... 1 ............................................ 3 ........................................... 3
No. 15A 240V .......................................................... - ............................................ - ........................................... -
No. 20A 240V .......................................................... - ............................................ 1 ........................................... 1
No. 30A 240V .......................................................... 1 ............................................ 1 ........................................... 1
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts ...................................10,000 .....................................10,000 ......................................10,000
BRYANT, INC. • 7310 WEST MORRIS STREET • INDIANAPOLIS, IN 46231
WEBSITE: www.bryant.com
PRINTED IN USA 11.04 CATALOG NO. 13AS-PA2 FORM SS-ASPAS07-01
All specifications are subject to change without notice.
Mechanical Dimensions (in inches)
Current No. of Height Width Depth
Rating Poles H1 H2 W1 W2
100 UL Listed 2 26.5 29.25 8.14 12.5 7
W1
W2
H1
H2
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug
100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14
Transfer Switch Features
• Electrically operated,
mechanically-held contacts for
fast, positive connections.
• Rated for all classes of load,
100% equipment rated, both
inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated
or silver alloy to resist welding
and sticking.
• Nema 1 enclosure is standard
on the 100 amp switch.
Conduit sizes
vary depending
on model #
Home Standby - 7kW - 12kW - 15kW
UL LISTED
PANEL BOARD