548J***D
SINGLE PACKAGE ROOFTOP
HEAT PUMP UNITS
WITH FIELD--INSTALLED ELECTRIC HEAT
SIZES 08--14 WITH PURON
R
(R--410A) REFRIGERANT
Submittal Data
Certified to ISO
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
9001
DESCRIPTION
548J***D units are one--piece, two--stage heat pump units
that are low profile, prewired, tested and charged at the
factory. These units have field convertible supply and return
openings and are intended for installation on a roof curb
accessory (ordered separately), or for slab mounting (for
horizontal duct connections). Units are designed to accept
field--installed electric heaters. Units may be ordered with
various factory--installed options. Field--installed accessories
are also available.
STANDARD FEATURES
Base Unit
S Puron (R--410A) HFC refrigerant
S SEER’s up to 13.4, EER’s up to 11.2
S IEERs:
up to 12.2 with single speed indoor fan motor
up to 12.5 with 2--speed/VFD indoor fan motor
S HSPF’s up to 7.7 and COP’s up to 3.3
S ASHRAE 90.1 compliant
S Rated in accordance with AHRI Standard 340
S Designed in accordance with Underwriters’
Laboratories Std 1995 and listed by UL and UL, Canada
S Two--stage cooling capacity control
S Non--corrosive composite sloping design; side or center
drain condensate pan. Meets ASHRAE Standard 62
S Cooling operating range from 25_Fupto115_F
(--4_Cupto46_C). Field installed accessory extends
the minimum down to --20_F(--29_C)
S Convertible from vertical to horizontal airflow for slab
mounting
S Two--inch disposable return air filters
S Thru--the--bottom power entry capability
S Single point electric connections on field--installed
electric heat units
S 24--volt control circuit protected with resettable circuit
breaker and 75--VA transformer
S Belt drive, constant torque, permanently lubricated
evaporator--fan motor on all size units.
S Totally enclosed condenser motors with permanently
lubricated bearings
S State--of--the--art defrost control board, easily configured
for defrost cycles of 30, 60, 90, or 120 minutes.
S Central Terminal Board for component and unit wiring
connections.
S Loss of Charge, High--Pressure, and Freeze Protection
switches
S Full perimeter base rail with built--in rigging adapters
andforktruckslots.
Cabinet
S Access panels with easy grip handles
S Innovative, easy starting, no strip screw features on unit
access panels.
S Pre--painted exterior panels and primer--coated interior
panels tested to 500 hours salt spray protection
S Fully insulated cabinet
S Tool--less filter access door
Refrigerant System
S Acutrolt refrigerant metering system
S Liquid line filter drier
S Scroll compressors with internal line--break overload
protection
S Indoor and outdoor coils constructed of aluminum fins
mechanically bonded to seamless copper tubes.
S Removable gauge line plugs for reading refrigerant
pressure with unit panels in place
S Four--way reversing valve operation
S Suction Line Accumulator standard -- prevents
excessive liquid flood back of refrigerant to the
compressor even during the start of the defrost cycle.
Standard Parts Warranty
S 5--year electric heater (field--installed)
S 5--year compressor
S 1--year parts
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - Submittal Data

548J***DSINGLE PACKAGE ROOFTOPHEAT PUMP UNITSWITH FIELD--INSTALLED ELECTRIC HEATSIZES 08--14 WITH PURONR(R--410A) REFRIGERANTSubmittal DataCertified t

Pagina 2 - ELECTRICAL DATA

10CERTIFIED DIMENSION 548J*14DC14195548J***D

Pagina 3 - OPTIONAL WARRANTIES

11ROOF CURB DETAILS — SIZES 08--127/16"[11]4 9/16"[115.5]1/4"[7.0]"A"1 3/4"[44.5]1 3/4"[44.4]20-3/4"[513]INSID

Pagina 4 - FIELD INSTALLED ACCESSORIES

12ROOF CURB DETAILS — SIZE 14C10365Manufacturer reserves the right to discontinue, or change at any ti me, specifications or designs without notice an

Pagina 5

2SUBMITTAL DATAJob NameArchitectEngineerContractorUnit DesignationPERFORMANCE DATAUnit Operating Weight lbCoolingNet Total Capacity BtuhNet Sensible C

Pagina 6

3FACTORY--INSTALLED OPTIONS (FIOPs)j Economizer with DRY BULB sensing and barometricreliefStandard Air Leak Dampers —f Models with W7212 controller pr

Pagina 7 - CERTIFIED DIMENSION 548J*12D

4FIELD INSTALLED ACCESSORIESj Economizer with DRY BULB sensing and barometricreliefStandard Air Leak Dampers —f Models with W7212 controller provides

Pagina 8

5CERTIFIED DIMENSION 548J*08 -- 09DC12051548J***D

Pagina 9

6CERTIFIED DIMENSION 548J*08 -- 09DC12052548J***D

Pagina 10 - CERTIFIED DIMENSION 548J*14D

7CERTIFIED DIMENSION 548J*12DC12053548J***D

Pagina 11 - 548J***D

8CERTIFIED DIMENSION 548J*12DC12054548J***D

Pagina 12 - ROOF CURB DETAILS — SIZE 14

9CERTIFIED DIMENSION 548J*14DC14194548J***D