Bryant 569F Manual de usuario Pagina 22

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 21
22
OPERATING SEQUENCE
569D072-120, 576C090-120 Units
At start-up, the thermostat calls for cooling. With all safety
devices satisfied, the compressor contactor and fan contactor
energize, causing the compressor and outdoor-fan motor to
operate. Thermostat contacts energize, allowing the field-
supplied and field-installed indoor-fan contactor to function.
A field-supplied and field-installed liquid line solenoid valve
also opens, allowing the system to function in Cooling mode.
As cooling demand is satisfied, the thermostat contacts
break, deenergizing the contactor and causing the system to
shut off. The liquid line solenoid valve closes, minimizing the
potential for refrigerant migration. The compressor does not
restart until the thermostat again calls for cooling. The
system is protected with a safety circuit so that the system
will not start if a fault exists (i.e., high or low pressure fault).
To reset the safety circuit, set the thermostat to eliminate
the cooling demand, then return to original set point. This
should be done only once, and if system shuts down due to
the same fault, determine the problem before attempting to
restart the system.
569F120 Units
When the thermostat calls for stage one cooling at start-up,
and all safety devices are satisfied, the compressor contactor 1
(C1) energizes causing compressor no. 1 and outdoor-fan
motor no. 1 to start (the indoor-fan contactor should be wired
to start at the same time as the compressor). The liquid line
solenoid (LLS) valve will open when compressor no. 1 starts,
allowing refrigerant to flow in the system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 and
outdoor-fan motor no. 2 to start. As the cooling demand
decreases, stage two on the thermostat opens, causing com-
pressor no. 2 and outdoor-fan motor no. 2 to shut down. As
the cooling continues to decrease, stage one of the thermo-
stat opens causing compressor no. 1 and outdoor-fan motor
no. 1 to shut down. The LLS valve for each compressor will
close when the associated compressor stops, minimizing the
potential for refrigerant migration during the off cycle.
The indoor-fan motor will stop if the thermostat is set to
AUTO and will continue to operate if the thermostat is set to
CONT. Each compressor is protected with a Cycle-LOC
TM
device so that the compressor will not operate if there is a
high-pressure fault, low-pressure fault, or a compressor is off
due to internal line break overcurrent/over temperature pro-
tection. To reset the Cycle-LOC device, set the thermostat
higher to remove the cooling demand, then return to the
original set point. This should be done only once. If the sys-
tem shuts down with the same fault, the cause for the fault
should be determined and corrected before the a Cycle-LOC
device is reset again.
566E150-240 Units
At start-up, when the thermostat calls for first stage cooling
and all safety devices are satisfied, the compressor contactor
(C1) energizes causing compressor one and fan motor one to
start. Fan motor no. 2 will start when the fan cycling pres-
sure switch (FCPS) closes as discharge pressure builds. With
the indoor-fan contactor wired to TB2-4 and TB2-9 contacts
on the terminal block, the indoor-fan will also start with the
compressor. The liquid line solenoid (LLS) valve will open
when compressor no. 1 starts, allowing refrigerant to flow in
the system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 to
start. As the cooling demand decreases, stage two on the
thermostat opens, causing compressor no. 2 to shut down. As
the cooling continues to decrease, stage one of the thermo-
stat opens causing compressor no. 1 and outdoor-fan motor to
shut down. The LLS valve for each compressor will close
when the associated compressor stops, minimizing the
potential for refrigerant migration during the off cycle.
The indoor-fan motor will stop if the thermostat is set to
AUTO and will continue to operate if the thermostat is set on
CONT. Each compressor is controlled by the thermostat so
they will not start until there is a demand from the thermo-
stat. Each compressor is protected with a Cycle-LOC
device
so that the compressor will not operate if there is a high-
pressure fault, low-pressure fault, or compressor is off due to
internal line break overcurrent/overtemperature protection.
To reset the a Cycle-LOC device, set the thermostat higher to
remove the cooling demand, then return to the original set
point. This should be done only once. If the system shuts
down with the same fault, the cause for the fault should be
determined and corrected before the a Cycle-LOC device is
reset again.
Vista de pagina 21
1 2 ... 17 18 19 20 21 22 23 24

Comentarios a estos manuales

Sin comentarios