
46
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
TO OPEN
DRAIN
A94054
Fig. 46 -- Example of Field Drain Attachment
PERSONAL INJURY HAZARD
Caution should be taken to prevent draining where slippery
conditions may cause personal injuries.
Excessive condensate draining may cause saturated soil
conditions which could result in damage to plants.
!
WARNING
CONDENSATE DRAIN PROTECTION
Freezing condensate left in condensate trap and drain line may
cause cracks, and possible water damage may occur. If freeze
protection is required, use condensate freeze protection accessory
or equivalent 3 to 6 watt per ft at 120-v and 40°F(4°C)
self-regulating, shielded, and waterproof heat tape. See
Installation Instructions supplied with accessory or heat tape
manufacturer’s recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back.
(See Fig. 47.)
3. Use wire ties to secure heat tape in place. Wire ties can be
positioned in notches of condensate trap sides. (See Fig.
47.)
4. Wrap field drain pipe with remaining heat tape,
approximately 1 wrap per ft.
5. When using field-supplied heat tape, follow heat tape
manufacturer’s instructions for all other installation
guidelines.
START-UP ADJUSTMENT AND
SAFETY CHECK
FURNACE MAY NOT OPERATE
Failure to follow this caution may result in furnace operation
stopping and water pipes freezing during cold weather.
Furnace control must be grounded for proper operation, or
control will lockout. Control is grounded through green/yellow
wire connected to gas valve C-terminal and burner box screw.
CAUTION
!
CONDENSATE TRAP
WIRE TIE(S)
HEAT TAPE
(3 WRAPS MINIMUM)
A93036
Fig. 47 -- Condensate Trap Heat Tape
Step 1 -- General
The furnace must have a 115-v power supply properly connected
and grounded.
NOTE: Proper polarity and proper grounding must be
maintained for 115-v wiring. If polarity is incorrect, control status
indicator light will flash rapidly and the furnace will not operate.
Natural gas service pressure must not exceed 0.5 psig (14-in. wc),
andbenolessthan0.16psig(4.5-in.wc).
Thermostat wire connections at R and W/W1 are the minimum
required for gas heating operation. W2 must be connected for
2-stage heating thermostats. C
OM, Y/Y2, and G are required for
cooling, heat pumps, and some clock thermostats. These must be
made at the 24-v terminal block on the control. (See Fig. 37.)
This furnace can be installed with either a single-stage heating or
a 2-stage heating thermostat.
For single-stage thermostats, connect thermostat W to W/W1 at
furnace control terminal block. (See Fig. 31 and 50H.) For
single-stage thermostats, the control will determine, based on
length of previous heating on and off cycles, when to operate in
low- and high-gas heat for optimum comfort. Setup switch-1
(SW-1) must be in the factory-shipped OFF position. See Fig. 36
and Table 11 and 12 for setup switch information.
352AAV
Comentarios a estos manuales