
47
A99118
Fig. 48 -- Inducer Housing Drain Tube Cap
If a 2-stage heating thermostat is to be used, move SW-1 to ON
position at end of furnace installation. This overrides built-in
control process for selecting high and low fire and allows the
2-stage thermostat to select gas heating modes. The W2 from
thermostat must be connected to W2 on control terminal block.
(See Fig. 32 and 50--57.)
Before operating furnace, check each flame rollout manual reset
switch for continuity. If necessary, press and release button to
reset switch. The blower compartment door must be in place to
complete the 115-v circuit to the furnace.
A99119
Fig. 49 -- Filling Condensate Trap
FIRE HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
This furnace is equipped with a manual reset limit switch in
the burner box area. The switch will open and shut off power
to the gas valve if a flame rollout or overheating condition
occurs in the burner enclosure area. DO NOT bypass the
switch. Correct inadequate combustion-air supply, component
failure, or restricted flue gas passageway before resetting
the switch.
CAUTION
!
Step 2 -- Prime Condensate Trap With Water
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may not
occur. The condensate trap has internal chambers which can
ONLY be primed by pouring water into the inducer drain side
of condensate trap.
CAUTION
!
1. Remove upper inducer housing drain connection cap. (See
Fig. 48.)
2. Connect field-supplied 1/2-in. (13 mm) ID tube to upper
inducer housing drain connection.
3. Insert field-supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run
through inducer housing, overfill condensate trap, and
flow into open field drain. (See Fig. 49.)
5. Remove funnel and tube from inducer housing and replace
drain connection cap and clamp.
Step 3 -- Purge Gas Lines
After all connections have been made, purge the gas lines and
check for leaks.
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in a fire, explosion,
personal injury, or death.
never purge a gas line into a combustion chamber. Never test
for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections, as specified in “Gas Piping”
and “Start-up Adjustment, and Safety Check” sections of
these instructions.
!
WARNING
Step 4 -- Sequence of Operation
Using schematic diagram in Fig. 36, follow the sequence of
operation through the different modes. Read and follow diagram
very carefully.
NOTE: If power interruption occurs during “call for heat”
(W/W1 or W/W1 and W2), the control will run the blower for the
selected blower off delay period after power is restored, if the
thermostat is still calling for gas heating. The amber LED will
flash code 12 during this period, after which the LED will be ON
continuous as long as no faults are detected. After this period, the
furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted
through blower door interlock switch ILK to furnace control
352AAV
Comentarios a estos manuales