SSP-SVX15C-EN
25
Charging Charts and Superheat
Figure 18. TWA090A
1
A
dd cha rge
R
emove
charge
Figure 19. TWA120A
1
A
dd cha rge
R
emove
charge
Figure 20. TWA180B
1
25
150
175
200
225
250
275
300
325
350
375
400
425
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Dis cha rge P re s s ure, ps ig
Liquid Temperature Le aving OD Coil, °F
TWA180B Cha rging Cu rve
A
dd cha rge
R
emove
charge
Figure 21. TWA240B
1
25
150
175
200
225
250
275
300
325
350
375
400
425
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Dis cha rge Pres sure, ps ig
Liquid Tem perature Lea vin g OD Coil, °F
TWA240B Charging Curve
A
dd cha rge
R
emove
charge
Table 6. TWA superheat with matched TWE air handler
Condenser Air Handler
Cooling Superheat Heating Superheat
Circuit 1 Circuit 2 Circuit 1 Circuit 2
TWA090A TWE090A 16.0 15.7
TWA120A TWE120A 16.3 13.1
TWA180B TWE180B 15.5 15.5 12.2 12.2
TWA240B TWE240B 14.7 14.7 11.4 11.4
Notes:
1. An adjustable TXV is provided for each circuit in the TWE and TWA models. If the application causes the superheat to deviate from the values shown
above by more than 1 degree - after the system has achieved steady state - the TXV should be adjusted to provide the values shown as measured at
the compressor.
2. The values given above have been tested and are approved for the matched sets shown. If an alternate combination is used, an expansion device
should be used that provides 16-20°F degrees of superheat measured at the compressor.
3. Check and adjust superheat using this table, then compare with charging chart to determine if charge corrections are necessary.