SSP-SVX15C-EN
Start-Up
ReliaTel Controls
The ReliaTel Control is a microelectronic control
feature, which provides operating functions that are
significantly different than conventional
Electromechanical units. The ReliaTel Refrigeration
Module (RTRM) uses proportional/integral control
algorithms to perform specific unit functions that
govern the unit operation in response to application
conditions.
The RTRM provides compressor anti-short cycle (ASC)
timing functions through minimumOOffff and OOnn
timing to increase reliability, performance and to
maximize unit efficiency. Upon power initialization, the
RTRM performs self-diagnostic checks to insure that all
internal controls are functioning. It also checks the
configuration parameters against the components
connected to the system. The system LED located on
the RTRM module is turned OOnn within one second
after power-up if all internal operations are correct.
The heating and cooling cycles of the heat pump are
automatic for Heat and Cool functions when using an
optional automatic changeover thermostat (TS).
The fan switch on the optional automatic changeover
thermostat can be placed in either the OONN position,
causing continuous evaporator (indoor) fan operation,
or the AAUUTTOO position causing fan operation to coincide
with heating or cooling run cycles. (In AAUUTTOO position,
the fan switch automatically changes to Heat or Cool in
response to sufficient room temperature change.)
Terminology
The following terms and acronyms may be used in this
section.
ASC
Anti-Short Cycle Timer
CC
Compressor Contactor
CCH Crankcase Heater
CF
Outdoor Fan Capacitor
CHR
Crankcase Heater Relay
COMM Communication Interface Module
CPR
Compressor
CTS
Coil Temperature Sensor
DTL
Discharge Temperature Limit Switch
EDC
Evaporator Defrost Control Switch
FTB Outdoor Fan Terminal Block
HPC
High Pressure Cutout Switch
HTB
High Voltage Terminal Block
LPC Low Pressure Cutout Switch
LTB
Low Voltage Terminal Board
OAS
Outdoor Air Temperature Sensor
ODF
Outdoor Fan Relay
ODM Outdoor Fan Motor
PM Phase Monitor
RTRM
ReliaTel Refrigeration Module
SOV Switchover Valve
TNS Transformer
Functions and Features
These subsections describe the following key heat
pump functions and features:
Processing Activated When the Disconnect Switch
is in OONN Position
Mechanical Heat
Auxiliary Heat
Emergency Heat
Cooling
Demand Defrost
Processing Activated When the Disconnect
Switch is in the ON Position
The following table lists the processing that occurs
given the stated condition.