GUIDE SPECIFICATIONS
SINGLE--PACKAGED AIR CONDITIONER AND GAS
FURNACE SYSTEM CONSTANT VOLUMEAPPLICATION
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 2 TO 5 TONS, NOMINAL (COOLING)
40,000 to 130,000 Btuh
Nominal Heating Input
MODEL NUMBER: 577D----A
PART I -- GENERAL
SYSTEM DESCRIPTION
Outdoor rooftop or ground mounted air conditioner and gas
furnace system utilizing a two--stage scroll compressor for cool-
ingduty. Unitshalldischarge supply airvertically orhorizontally
as shown on contract drawings. Outdoor fan/coil section shall
have a draw--thru design with vertical discharge for minimum
sound levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with AHRI Standards
210/240, and 270.
B. Unit shall be designed in accordance with UL Standard
1995 and ANSI Z21.47.
C. Unit shall be manufactured in a facility registered to ISO
9001 manufacturing quality standard.
D. Unit shall be UL listed and c--UL certified as a total
package for safety requirements.
E. Roof curb shall be designed to conform to NRCA
Standards.
F. Insulation and adhesives shall meet NFPA 90A
requirements for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer’s recommen-
dations.
PART 2-- PRODUCTS
EQUIPMENT
A. General:
Factory--assembled, single--piece, heating and cooling unit.
Contained within the unit enclosure shall be all factory wiring,
piping, controls, refrigerant charge (R--410A), and special fea-
tures required prior to field start--up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated, zinc--coated,
prepainted steel capable of withstanding 500 hrs of salt spray.
2. Normal service shall be through 3 removable cabinet panels.
3. The unit shall be constructed on a rust proof unit base thathas
an externally trapped, integrated sloped drain pan.
4. Indoor fan compartment top surface shall be insulated with a
minimum 1/2--in. (13 mm) thick, flexible fiberglass
insulation, coated on the airside and retained by adhesiveand
mechanical means. The indoor wall sections will be insulated
with a foil--faced insulation capable of being wiped clean.
Aluminum foil--faced fiberglass insulation shall be used in the
entire indoor air cavity seciton.
5. Unit shall have a field--supplied condensate trap.
C. Fans:
1. The indoor fan shall be ECM Motor, as shown on equipment
drawings.
2. Fan wheel shall be made from steel, be double--inlet type. It
shall have forward--curved blades with a corrosion--resistant
finish and shall be dynamically balanced.
3. Outdoor fan shall be of the direct--driven propeller type with
aluminum blades, riveted to corrosion--resistant steel spiders.
Itshall be dynamically balanced, and discharge air vertically.
D. Compressor:
1. Fully hermetic 2--stage compressors with factory--installed
vibration isolation.
2. Two--stage scroll compressors shall be standard on all units.
E. Coils:
1. Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed.
2. Tube sheet openings shall be bellied to prevent tube wear.
F. Heating Section:
1. Induced--draft combustion type with energy saving direct
spark ignition system and redundant main gas valve.
2. Pressure switch ensures adequate airflow for combustion
from induced draft motor.
3. The heat exchangers shall be constructed of 409 stainless
steel for corrosion resistance.
4. Burners shall be of the in--shot type constructed of
aluminum coated steel.
5. All gas piping and electric power shall enter the unit cabinet
at a single location.
G. Refrigerant Metering Device:
Refrigerant metering device shall be of the TXV
(thermostatic expansion valve) type.
H. Filters:
Filter section shall consist of field--installed, throw--away,
1--in. (25 mm) thick fiberglass filters of commercially
available sizes.
I. Controls and Safeties:
1. Unit controls shall be complete with self--contained low
voltage control circuit.
2. Units shall incorporate an internal compressor protector that
provides reset capability.
3. Unit shall provide high and low/loss--of--charge pressure
safety protection.
J. Operating Characteristics:
1. Unit shall be capable of starting and running at 125°F
(51.6_C) ambient outdoor temperature, ex
ceeding maximum
load criteria of AHRI Standard 210.
2. Unit shall be capable of low ambient cooling from 55°F
(12.7_C) down to 0°F (--17.7°C) ambient outdoor
temperature with low ambient cooling enabled on the UI
3. Units shall be provided with fan time delay to prevent cold air
delivery before the heat exchanger warms up.
K. Electrical Requirements:
Allunitpowerwiring shall enter unitcabinet ata singlelocation.
L. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearingsand
inherent automatic--reset thermal overload protection.
3. Outdoor fan motor shall be totally enclosed.
4. Evaporator fan motor to be ECM motor.
577D-- -- A