18
Input 5 -- This input is a discrete input and can be
configured to be one of six different functions: No Function,
Fire Shutdown, Fan Status, Filter Status, Remote Occupancy,
or Door Contact. This input can also be configured to be
either a Normally Open (N/O) or a Normally Closed (N/C)
switch. Input 5 is factory wired to pin J1-10. Field
accessories can be wired to its parallel pin J5-3.
Software Default = Fire Shutdown and N/C
Factory Default = Fire Shutdown and N/O
Input 8 -- This input is a discrete input and can be
configured to be one of six different functions: No
Function, Enthalpy Switch, Fan Status, Filter Status,
Remote Occupancy, or Door Contact. This input can also
be configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 8 is factory wired to
pin J2-6. Field accessories can be wired to its parallel pin
J5-1.
Software Default= Enthalpy Switch and N/O
Factory Default = No Function and N/O without
factory installed enthalpy sensor
Input 9 -- This input is a discrete input and can be
configured to be one of seven different functions: No
Function, Humidistat, Fan Status, Filter Status, Remote
Occupancy, or Door Contact. This input can also be
configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 9 is factory and field
wiredtopinJ5-7.
Factory Default = Humidistat and N/O
Space Sensor Type – This tells the controller what type
of space sensor is installed to run the unit. The four types
that can be used are: a standard 10k Type II thermistor
(T55), sensor with a setpoint offset slider bar (T56), or a
communicating sensor (SPT Sensor) and, ZS Sensor.
Range =T55, T56 (Use for T59), SPT Sensor,
or ZS Sensor
Default = T55
ZS Sensor Type -- The type of local space temperature
sensor.
Range =ZS Base, ZS Plus, ZS Pro
Default = None
T5x Override Duration – Sets the override time duration
the unit will change from unoccupied to occupied when
the override button is pushed on the space sensor.
Range = 0-24 hours Default = 1 hour
Rnet Port -- input for communicating sensor
Range = SPT Sensor or ZS Sensor
Default= None
Service Configuration
Unit Type – This tells the control what type of unit it is
controlling. Heat/Cool refers to gas and electric heat units.
HP O/B Ctrl refers to a heat pump unit which requires
reversing valve control. HP Y1/W1 Ctrl refers to a heat
pump unit whose reversing valve is built in to the cooling
or heating call. This decision is factory configured for the
specific unit type as supplied.
Compressor Stages – This refers to the number of
mechanical cooling stages available on a specific unit.
Factory Default = “One Stage” for 1 compressor
units or “Two Stages” for 2
compressor units.
Economizer Exists – This indicates if there is an
economizer installed on the unit.
Factory Default =NO if no economizer, or YES if
there is an economizer installed
Fan Control -- This refers to the type of fan control for
the unit.
Range = Single Speed, Two Speed,
or Variable Speed
Factory Default = Single Speed --
(04--07 and A08--A12)
Two Speed--
(units with VFD option)
VFD Input -- Defines the electrical control signal used by
the VFD’s input.
Range = 2--10VDC or 0--10VDC
Factory Default = 2--10 VDC
Max VFD Output --ThemaximumVFDsignalRTUOpen
supplies to the VFD as a percentage of its range. The
balancer can set this to adjust the unit’s maximum airflow.
Applies to Variable Speed fan control.
Range = 33--100% Default = 100%
Min VFD Output -- The minimum VFD signal RTU Open
supplies to the VFD as a percentage of its range. The
balancer can set this to adjust the unit’s minimum airflow.
Applies to Variable Speed fan control only.
Range = 33--100% Default = 40%
Dehum Min VFD Output -- The minimum output signal
supplied by RTU Open during dehumidification as a
percentage of its range. Applies to Variable Speed fan
control only .
Range = 50--100% Default = 100%
Stage 1 SAT Setpoint -- The VFD Supply Air Setpoint
during stage 1 cooling. Must be at least 4_F greater than
Minimum Cooling SAT parameter
Range = 45 -- 75_F Default = 57_F
Stage 2 SAT Setpoint -- The VFD Supply Air Setpoint
during stage 2 cooling. Must be at least 4_F greater than
Minimum Cooling SAT parameter
Range = 45 -- 75_F Default = 57_F
Stage 3 SAT Setpoint -- The VFD Supply Air Setpoint
during stage 3 cooling. Must be at least 4_F greater than
Minimum Cooling SAT parameter
Range = 45 -- 75_F Default = 56_F
Heat Type – Indicates the type of heat which is installed in
the unit. Electric is any unit without gas and a Gas unit is
one which requires gas input for heating.
Factory Default = Gas for gas units and Electric for
all other units (cooling only units and heat pumps)
TS---5580J---02