
28
Alarms
Alarms are provided to indicate a possible problem with
the controller or unit. Alarms can be checked through a
network and/or the local access device. All alarms are
listed in Table 4 with name, object name, action taken by
control, reset method, and possible cause. Some alarms
can occur based on specific configurations.
Safety Chain Alarm
This alarm occurs immediately if a field installed,
normally closed, safety contact opens and interrupts
24VAC signal input #4 (J1--9). The Unit Status will be
Shutdown and the System Mode will be Disable. All unit
operations stop immediately and will not restart until the
alarm automatically clears. There are no configurations
for this alarm; it is all based on field installed wiring. This
alarm will not occur if Fire Shutdown Alarm is active.
Normal operation resumes when the safety chain circuit is
complete.
Fire/Smoke Shutdown Alarm
This alarm occurs immediately when the smoke detector
senses smoke. The Unit Status will be Shutdown and the
System Mode will be Disable. All unit operations stop
immediately and will not restart until the alarm
automatically clears. If there is not a smoke detector
installed or the smoke detector did not trip, check input
configurations.
NOTE: The default function for input 5 is a normally
open Fire Shutdown input.
Gas Valve Alarm
This alarm occurs 60 second after gas heat has been
de--energized but the Integrated Gas Control (IGC) board
is still indicating a need for fan operation. Upon alarm
detection, the fan will start immediately and run at its
highest speed.
Supply Fan Failure
This alarm occurs when the indoor fan is being command
on and the fan status switch feedback is showing the fan
off. This will end current operating mode and disable unit
operation. This alarm requires a fan status switch to be
configured on one of the inputs.
Supply Fan in Hand
This alarm occurs when the indoor fan is being
commanded off and the fan status switch feedback is
showing the fan is on. This will prevent any operating
mode and disable unit operation. This alarm requires a fan
status switch to be configured on one of the inputs.
Compressor Status
This alarm indicates the base unit’s compressor safety
circuit is energized. Cooling, heating, and supply fan
outputs are not interrupted. Normal operation resumes
when the compressor safety circuit is de-energized. This
alarm requires field use of this described compressor
safety circuit.
Space Temp Sensor
This alarm occurs if the space sensor wired to the RTU
Open is disconnected or shorted for more than 10 seconds or
if the SPT value from the Network is no longer being
received. When this occurs the Unit Status will be Shutdown
and the System Mode will be Run. Sensor, sensor
connections, wiring, board connection, and configurations
should be checked for faults or errors. Alarm will reset
automatically when cause is fixed.
ZS Sensor
This alarm occurs if the ZS sensor wired to the RTU Open
stops communicating with the controller.
ZS Sensor -- This alarm indicates a communication
failure of a connected ZS sensor that previously had been
actively communicating. The alarm is reset when normal
ZS sensor communications resume, if power is cycled to
the controller, or if the Shutdown point is set to Active.
ZS Configuration -- This alarm indicates that at least one
ZS sensor is configured in the Sensor Binder properties
and is not actually communicating. The alarm is reset
when the configured ZS sensor is communicating or the
configuration is changed to reflect the sensor is no longer
connected to the Rnet.
Supply Air Temp Sensor
This alarm occurs immediately when the supply air
temperature sensor wired to the RTU Open is
disconnected or shorted. When this occurs the Unit Status
will be Shutdown and the System Mode will be Run.
Sensor, sensor connections, wiring, board connection, and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
Local OAT Sensor
This alarm occurs when the outdoor air sensor indicates a
short or open circuit or the Network OAT value is no
longer being received. Economizer cooling and optimal
start functions are disabled. Normal operation resumes
when the controller detects a valid sensor.
Outdoor Air Temp Sensor
This alarm indicates that a valid OAT sensor value is no
longer available to the controller after having been
available previously.
Economizer Operation -- This alarm is active whenever
an economizer fault is detected as required by California
Title 24 Economizer FDD logic. Once detected, this alarm
will stay active until the Shutdown input is set to Active
or the fan is stopped.
Economizer -- This point indicates the specific fault
detected and annunciated by the Economizer Operation
alarm above. Detected fault conditions include: Failed to
Fully Open, Failed to Open, Failed to Close, and Stuck
Open.
Space Relative Humidity Sensor
This alarm indicates the mA input at the associated
channel falls below 3.5 mA or rises above 21 mA, or the
Network value for space RH is no longer being received.
Cooling, heating, and supply fan operation continues,
however, the controller’s Perfect Humidityt binary
output is disabled until the fault condition is corrected.
IAQ Sensor
This alarm indicates the mA input at the associated
channel falls below 3.5 mA or rises above 21 mA, or the
Network value for space RH is no longer being received.
Cooling, heating, and supply fan operation continues.
However, the controller’s IAQ control function is disabled
until the fault condition is corrected.
TS---5580J---02
Comentarios a estos manuales