APPENDIX A -- USER INTERFACE MENUS (CON’T)
Field Assistant Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
STATUS
Properties>Control Program
>Status
3, 2, 1 Equipment Status mode_status 1=Disabled
2=Test
3=Run
3,2,1 System Mode run_status 1=Off
2=Fan Only
3=Economizer Cooling
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling
10=Fire Shutdown
11=IAQ Override
12=Pre-occ Purge
Supply Fan Status
1
sfan_status Off/Running
Fan / Speed fan_run 1=Off
2=Low
3=Med
4=High
5=On
3,2,1 Supply Fan VFD
2
vfd_output 0-100 %
3,2,1 Space Temperature - Prime Variable space_temp xxx °F
3,2,1 Supply Air Temperature sa_temp xxx °F
3,2,1 Outdoor Air Temperature oa_temp xxx °F
3,2,1 Space Relative Humidity space_rh 0-100 %
3,2,1 Indoor Air CO2 iaq 0-5000 ppm
3,2,1 Outdoor Air CO2 oaq 0-5000 ppm
3,2,1 Economizer Output econ_output 0-100 %open
3,2,1 Shutdown shutdown Inactive/Active
UNIT CONFIGURATION
Properties>Control Program>
Configuration>
Unit Configuration
3 Fan Mode fan_mode 1=Auto
2=Continuous
3=Always On
Continuous
3 Power Fail Restart Delay start_delay 0-30 sec 5
Fan Off Delay fan_delay_off 0-180 sec 90
3 Minimum Cooling SAT sat_cl_min 45-75_F 50
3 Maximum Heating SAT sat_ht_max 85-150_F 120
N/A Vent Dmpr Pos / DCV Min Pos econ_min 0-100% Open 20
N/A Economizer Purge Min Pos econ_purge_min 0-100% Open 40
N/A LowFanEconMinPos
3
econ_min_2 0-100% Open 33
N/A DCV Max Vent Damper Pos iaq_dpr_max 0-75% Open 50
3 Supply Fan Service Alarm Timer sfan_service_hrs 0-9999 hr 600
N/A Comp 1 Service Alarm Timer comp1_service_hrs 0-9999 hr 0
N/A Comp 2 Service Alarm Timer comp2_service_hrs 0-9999 hr 0
3 Filter Service Alarm Timer filter_service_hrs 0-9999 hr 600
N/A Door Alarm Delay door_alarm_delay 0-180 sec 60
3 Pushbutton Override pb_enable Disable/Enable Enable
3 Setpoint Adjustment stpt_adj_enable Disable/Enable Enable
3 Setpoint Adjustment Range stpt_adj_range +/-0-5_F 5
3 Cooling Lockout Temperature oat_cl_lockout 0-80_F 45
3 Economizer High OAT Lockout Temp oat_ec_lockout 55-80_F 75
N/A HP Rev Cycle Lockout Temp
4
hp_rev_cycle_lockout -20-65_F -3
N/A HP Aux Heat Lockout Temp
4
oat_auxht_lockout -20-65_F 40
3 Heating Lockout Temperature oat_ht_lockout 35-150_F 65
N/A Pre Occupancy Purge preocc_purge Disable/Enable Disable
3 Purge Time purge_time 0-240 min 60 min
3 Unocc Free Cool ntfc_ena Disable/Enable Disable
N/A Min Setpoint Separation min_stpt_sep 2-10_F 5
N/A Occupancy Source occ_source 1=Always Occupied
2=BACnet Schedule
3=BAS on/off
4=Remote Occ Input
Always Occupied
1
= This point is only visible when Input 3, 5, 8, or 9 is configured for Fan Status
2
= This point is only visible when Fan Control is configured for Variable Speed
3
= This point is only visible when Fan Control is configured for Two Speed
4
= This point is only vi sible when Unit Type is configured for HP O/B Ctrl or HP Y1/W1 Ctrl
TS---5580J---02