APPENDIX A -- USER INTERFACE MENUS (CON’T)
Field Assistant Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
SERVICE CONFIGURATION
Properties>
Control Program>
Configuration>
Service Configuration
3 Unit Type unit_type 1=Heat/Cool
2= n/a
3=HP O/B Ctrl
4=HP Y1/W1 Ctrl
Heat/Cool
(580/558J and 581/55J models)
HP Y1/W1 Ctrl
(548J and 549J models)
3 Compressor Stages comp_stages 1=One Stage
2=Two Stages
One Stage (sizes 04-07, and A08-A12)
Two Stages (sizes 08-30)
N/A Face Split Coil
6
face_split Yes/No No
3 Economizer Exists econ_exist No/Yes No (No FIOP)
Yes (FIOP)
3 Fan Control fan_type 1=Single Speed
2=Two Speed
3=Variable Speed
Single Speed (04-07 and A08-12)
Two Speed (units with VFD option)
N/A VFD Input vfd_in_type 0-10Vdc/2-10Vdc 2-10Vdc
N/A Max VFD Output max_vfd_spd 33-100% 100%
N/A Min VFD Output min_vfd_spd 15-100% 40%
N/A Dehum Min VFD Output dehum_min_vfd 50-100% 60%
3 Reversing Valve Output
7
rev_vlv_type O output type/B output type O output type
3 Heat Type heat_type Electric/Gas Gas (580J/581J Series Units)
Electric (558J/551J/548J/549J
Series Units)
3 Number of Heat Stages heat_stages 1=1 stage
2=2 stages
3=0 stage
0 (558J/551J series cooling only
units)
1 (All 548J and 549J, Low Nox units,
single phase gas units,
580/558J04-09 low and
580/558J05-07 med heat 3 phase
gas units)
2 (580/558J04 and 08-09 med,
580/558J05-09 high heat 3 phase
gas units, 581/551J04-09 3 phase
gas units and All 12-30 gas units)
N/A Continuous Occupied Exhaust occ_exh No/Yes No
3 RH Control rh_enable Disable/Enable Enable (Units with Perfect Humidity™)
Disable (Units w/o Perfect Humidity™)
3 DCV Control dcv_enable Disable/Enable Disable
N/A Indoor CO2 Sensor Value @ Min mA iaq_ref_lo_ppm 0-9999ppm 0
N/A Indoor CO2 Sensor Value @ Max mA iaq_ref_hi_ppm 0-9999ppm 2000
N/A Outdoor CO2 Sensor Value @ Min mA oaq_ref_lo_ppm 0-9999ppm 0
N/A Outdoor CO2 Sensor Value @ Max mA oaq_ref_hi_ppm 0-9999ppm 2000
N/A System Space Temperature system_spt
N/A System Space RH system_rh
N/A System Space AQ system_iaq
N/A System Outdoor AQ system_oaq
N/A System Cool Demand Level cool_demand_level 0-3 0
N/A System Heat Demand Level heat_demand_level 0-3 0
N/A System Outdoor Air Temperature system_oat
6
= This point is visible when Fan Control is configured f or Variable Speed
7
= This point is visible when Unit Type is configured for HP O/B Ctrl
TS---5580J---02