
8
Resistive Non--Communicating Sensor Wiring
For sensor with setpoint adjustment up to 1000 ft (305m),
use three-conductor shielded cable 20 gauge wire to
connect the sensor to the controller. For non set point
adjustment (slidebar) or return air duct sensor, an
unshielded, 18 or 20 gauge, two-conductor, twisted pair
cable may be used. Below is the list of the connections of
the SPT to the RTU Open, refer to Fig. 5 and 6 for typical
connections at the sensor.
S J20-1 = temperature sensor input (SEN)
S J20-2 = sensor common
S J20-3 = Setpoint adjustment input (SET)
NOTE: See Fig. 7 for space temperature sensor averaging.
T55/56 Override button will no longer function when sensors
are averaged. Only Sensor 1 T56 STO input can be used.
2
3
45
61
SW1
SEN
SET
Cool Warm
BRN (GND)
BLU (SPT)
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
BLK
(T56)
C07131
Fig. 5 -- Space Temperature Sensor
Typical Wiring (33ZCT56SPT)
OR SET SEN
OPB COM- PWR+
BLU (SPT)
BLK (STO)
24 VAC
SENSOR
WIRING
POWER
WIRING
BRN (COM)
NOTE: Must use a separate isolated transformer.
J20-3
J20-2
J20-1
C10291
Fig. 6 -- Space Temperature Sensor
Typical Wiring (33ZCT59SPT)
Rnet Communicating Sensor Wiring
The Rnet bus allows local communication with the RTU
Open, including communicating sensors. The Rnet bus
can hold up to 6 devices in the following combinations
wired in daisy-chain or hybrid configuration:
S 1-4 ZS--BNK sensor(s)
S 1 ZSPL--BNK or ZSP--BNK sensor
S 1-4 SPS sensor(s), and 1ZSPL--BNK or ZSP--BNK sensor
S Any of the above combinations, plus CO
2
or RH
combination
NOTE: Additional ZS sensors must be addressed. Use
the jumpers on the ZS sensor’s circuit board and refer to
the sensor installation instructions for addressing.
For Rnet wiring up to 500ft (152m), use 18 AWG 4
conductor unshielded plenum rated cable. The RTU Open’s
J13-RNET connection has a 4 pin Phoenix connector wired
as described below, Fig. 8 shows sensor Rnet wiring.
S RNET -- 1 = Signal ground (GND)
S RNET -- 2 = Signal (Rnet+)
S RNET -- 3 = Signal (Rnet--)
S RNET -- 4 = Power (+12v)
Sensor Averaging
Non--communicating sensors:
See Fig. 7 for space temperature sensor averaging
configurations, only combinations of 4 or 9 sensors will
operate correctly.
NOTE: T55/T56 Override button will no longer function
when sensors are averaged. Only 1 T56 STO input can be
used. Non--communication CO
2
sensors can not be
averaged.
Communicating sensors:
Any combination of sensors described in the “Rnet
Communicating Sensor Wiring” section can be used.
NOTE: Communicating CO
2
sensors and RH sensors can
be averaged if within the realm described.
CO2 Sensor(s) (IAQ and OAQ)
The indoor air quality (IAQ) and outdoor air quality
(OAQ) sensors monitor carbon dioxide (CO
2
) levels. This
information is used to monitor the quality of air in terms
of parts per million (PPM). The same sensor is used for
inside, outside, and duct monitoring, except an aspirator
box is required for outside and duct mounting. The CO
2
sensor is preset for a range of 0 to 2000 ppm and a linear
mA output of 4 to 20. The rooftop unit may have a factory
installed CO
2
sensor on the side of the economizer
assembly in the return air section of the unit and is
pre-wired and pre-configured at the factory. For field
installed sensors, a field supplied transformer must be
used to power the sensor. Refer to the instructions
supplied with the CO
2
sensor for electrical requirements
and terminal locations. RTU Open configurations must be
changed after adding a CO
2
sensor. See below and Fig. 9
for typical CO
2
sensor wiring.
S J4--2 or J4--5 = 4--20mA signal input
S J4--3 or J4--6 = signal common
NOTE: The factory used J4-2&3 for CO
2
(IAQ) sensor
inputs.
TS---5580J---02
Comentarios a estos manuales