Table 1 RTU Open Inputs and Outputs
POINT NAME
BACnet OBJECT
NAME
TYPE OF I/O
CONNECTION PIN
NUMBER(S)
CHANNEL DESIGNATION
DEDICATED INPUTS
Space Temp / Zone Temp zone_temp AI (10K Thermistor) J 2 0 --- 1 & 2 Analog Input 10
Supply Air Temperature sa_temp AI (10K Thermistor) J 2 --- 1 & 2 Analog Input 6
Outside Air Temperature oa_temp AI (10K Thermistor) J 2 --- 3 & 4 Analog Input 7
Space Temperature Offset Pot stpt_adj_offset AI (100K Potent iomet er) J 2 0 --- 3 & 4 Analog Input 11
Safety Chain Feedback safety_status BI (24 VAC) J 1 --- 9 Binary Input 4
Compressor Safety Status
(1)
comp_status BI (24 VAC) J 1 --- 2 Binary Input 3
Fire Shutdown Status firedown_status BI (24 VAC) J 1 --- 1 0 Binary Input 5
Enthalpy Status enthalpy_status BI (24 VAC) J 2 --- 6 & 7 Binary Input 8
Humidistat Input Status humstat_status BI (24 VAC) J 5 --- 7 & 8 Binary Input 9
Zone Temperature n/a n/a J 1 3 --- 1 --- 4 Rnet
CONFIGURABLE INPUTS
(4)
Indoor Air CO2 iaq A I ( 4 --- 2 0 m A )
J 4 --- 2 & 3 o r J 4 --- 5 & 6
Analog Input 2
Outdoor Air CO2 oaq A I ( 4 --- 2 0 m A ) Analog Input 1
Space Relative Humidity space_rh A I ( 4 --- 2 0 m A ) Analog Input 10
Supply Fan Status
(2)
sfan_status BI (24 VAC)
J 5 --- 1 & 2 o r J 5 --- 3 & 4 ,
J 5 --- 5 & 6 o r J 5 --- 7 & 8
(3)
BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
Filter Status
(2)
filter_status BI (24 VAC) BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
Door Contact
(2)
door_contact_status BI (24 VAC) BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
Rem ote Occupancy input
(2)
occ_contact_status BI (24 VAC) BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
IGC input
(2)
igcovr_status BI (24 VAC) Binary Input 9. M a ndato ry input on gas hea t units.
OUTPUTS
Economizer Output econ_output AO (4--- 20mA) J 2 --- 5 Analog Output 1
Supply Fan VFD vfd_output AO ( 2 --- 1 0 Vd c ) J 2 2 --- 1 & 2 Analog Output 2
Supply Fan Relay sfan BO R elay (24VAC, 1A) J 1 --- 4 Binary Output 1 (G)
Cool 1 Relay State comp_1 BO Relay (24VAC, 1 A) J 1 --- 8 Binary Output 5 (Y1)
Cool 2 Relay State comp_2 BO Relay (24VAC, 1 A) J 1 --- 7 Binary Output 4 (Y2)
Cool 3 Relay State comp_3 BO Relay (24VAC, 1 A) J 1 1 --- 5 & 6 Binary Output 7 (Y3)
Heat 1 Relay State heat_1 BO Relay (24VAC, 1A) J 1 --- 6 Binary Output 3 (W1)
Heat 2 Relay State heat_2 BO Relay (24VAC, 1A) J 1 --- 5 Binary Output 2 (W2)
Power Exhaust Relay State pexh BO Relay (24VAC, 1 A) J11---2&3(N.O.) Binary Output 8 (PE)
Dehumidification Relay dehum BO R e lay (24VAC, 1A) J11---7&8(N.O.) Binary Output 6
(1)
Safety Chain Feedback: 24Vac required at this terminal to provide “ Run Enable status. See Input/Output section for additional instructions.
(2)
These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section for wiring and setup instructions.
(3)
Pa r al l e l p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u s e d f o r f i l e d i n s t a l l a t i o n .
(4)
Refer to the input configuration and accessory sections for more detail.
Sensors and Accessories
The RTU Open controller is configurable with the
following field-supplied sensors:
NOTE: Supply air temperature sensor (33ZCSENSAT) is
factory-installed.
S Space temperature sensor (ZS--BNK, ZS--C--BNK,
ZS--H--BNK, ZS--HC--BNK, ZSPL--C--BNK,
ZSPL--H--BNK, ZSPL--HC--BNK, ZSP--BNK,
ZSP--C--BNK, ZSP--H--BNK, ZSP--HC--BNK ,
33ZCT55SPT, 33ZCT56SPT, or 33ZCT59SPT)
S Indoor air quality sensor (ZS--C--BNK, ZS--HC--BNK,
ZSPL--C--BNK, ZSPL--HC--BNK, ZSP--C--BNK,
ZSP--HC--BNK, 33ZCSPTCO2--01,
33ZCSPTCO2LCD--01, 33ZCT55CO2--02, or
33ZCT56CO2--02) required for demand control
ventilation.
S Outdoor air quality sensor (33ZCSPTCO2--01,
33ZCSPTCO2LCD--01)
S CO
2
aspirator box (C33ZCCASPCO2) required for CO
2
return duct/outside air applications
S Outdoor air enthalpy switch (33CSENTHSW)
S Return air enthalpy sensor (33CSENTSEN) required for
differential enthalpy control
S Space relative humidity sensor (33ZCSENSRH-02)
S Duct relative humidity (33ZCSENDRH-02)
S Humidistat (--HL--38MG-029)
S Smoke Detectors (CRSMKSEN002A00,
CRSMKKIT002A00)
S Fan and/or Filter Status (CRSTATUS001A00,
CRSTATUS005A00)
User Interface
S Field Assistant (USB-TKIT required)
Install Analog Sensors
Supply Air Sensor (SAT)
The factory supplies the discharge (supply) air sensor with
the unit and is pre--wired.
Unit/Size SAT Shipping Location/Installation Location
580/558/581/551J 04--- 16
549J 04--- 12
548J 04--- 14
The SAT is secured to the unit’s supply duct
opening. This sensor must be relocated into
the supply duct during unit installation.
581/551J 17 --- 24
580/558/548J 17 ---30
The SAT is mounted through the side of the
heat chamber below the f an deck, and does
NOT require relocation.
OutdoorAirSensor(OAT)
The OAT is supplied with the economizer option or
accessory. It is wired through the 12-pin plug (PL6) in the
return air section of the unit and is mounted on the
economizer assembly.
Space Temperature Sensor (SPT)
There are 2 types of space temperature sensors available
from Bryant, resistive input non-communicating (T55, T56,
and T59) and Rnet communicating (ZS--BNK, ZS--C--BNK,
ZS--H--BNK, ZS--HC--BNK, ZSPL--C--BNK,
ZSPL--H--BNK, ZSPL--HC--BNK, ZSP--BNK, ZSP--C--BNK,
ZSP--H--BNK, ZSP--HC--BNK) sensors. Each type has a
variety of options consisting of: timed override button, set
point adjustment, a LCD screen, combination of humidity or
CO
2
sensing and communication tie in. Space temperature
can be also be written to from a building network or zoning
system. However, it is still recommended that return air duct
sensor be installed to allow stand-alone operation for
back-up. Refer to the configuration section for details on
controller configurations associated with space sensors.