Table 3 – LED’s
The LED’s on the RTU Open show the status of certain functions
If this LED is on... Status is...
Power The RTU Open has power
Rx The RTU Open is receiving data from the network segment
Tx The RTU Open is transmitting data over the network segment
BO# The binary output is active
The Run and Error LED’s indicate control module and network status
If Run LED shows... And Error LED shows... Status is...
2 fl ashes per second Off Normal
2 fl ashes per second 2 flashes, alternating with Run LED Five minute auto---restart d elay after system error
2 fl ashes per second 3flashes,thenoff Control module has just been formatted
2 fl ashes per second 4 flashes, then pause Two or more devices on this network have the same
MSTP network address
2 fl ashes per second On Exec ha lted after frequent system errors or control pro-
grams halted
5 fl ashes per second On Exec start---up aborted, Boot is running
5 fl ashes per second Off Firmware transfer in progress, Boot is running
7 fl ashes per second 7 flashes per second, alternating with
Run LED
Ten second recovery period after brownout
14 flashes per second 14 flashes per second, alternating with
Run LED
Brownout
On On Failure. Try the following solutions:
--- Turn the RTU Open off, then on.
--- F o r m a t t h e R T U O p e n .
--- Download memory to the RTU Open.
--- Replace the RTU Open.
Table4–RTUOpenAlarms
POINT NAME
BACnet Object
NAME
ACTION TAKEN BY
CONTROL
RESET METHOD PROBABLE CAUSE
Safety Chain safety_alarm Immediate Shutdown Automatic Over load Indoor Fan or Electric Heater
overheat
Fire Shutdown fire_alarm Immediate Shutdown Automatic Smoke detected by smoke detector or
configuration incorrect
Gas Valve igc_alarm Immediately operate fan at high-
est speed
Automatic Ga s valve stuc k open after heati ng cyc le,
causi ng heat to continue to operate.
Supply Fan sfan_fail_alarm Immediately disable
Operation
Automatic T ripped Circuit Breaker, Broken belt,
Bad indoor fan motor, Configuration
incorrect, Bad fan status switch.
Supply Fan in Hand sfan_han d_alarm Ramp down Operations Automatic Bad Fan Status Switch, Configuration
incorrect.
Compressor Status comp_alarm Alert Gener ated Automatic Compressor would not start
Space Temp Sensor spt_fail Ramp down Operations Automatic Bad sensor, bad wiring, failure to receive
Network or sensor configured incorrectly .
ZS Sensor zst_sensor_fail Alert Generated Automatic This alarm indicates a commun ication
failure of a connected ZS sensor that
previously had been actively
communicating.
ZS Configuration zs_config_ fail Alert Generated Automati c This alarm indicates that at least one ZS
sensor is configured in the Sensor
Binder properties and is not actually
communicating.
Supply Air Temp Sensor loc_sat_sensor_fail Ramp down Operations Automatic Faulty, shorted, or open thermistor
caused by wiring error or loose
connection.
Local OAT Sensor ioc_oat_sensor_fail May cause Economizer an d Low
ambient DX cooling lockout to be
disabled
Automatic Faulty, shorted, or open thermistor
caused by wiring error or loose
connection.
Outdoor Air Temp Sensor oat_fail Economizer an d Low ambient DX
cooling lockout disabled.
Automatic Failure to receive valid local or n etwork
value for Outdoor Air Temperature
Space Relative
Humidity Sensor
sprh_sensor_fail Dehumidification disabled Automatic Sensor reading is out of range. Bad
sensor, bad wiring, failure to recei v e
Network or sensor configured incorrectly.
TS---5580J---02