RTUOPENSTART--UPSHEET
RTU Model Number: Date:
RTU Serial Number:
Performed by:
RTU Open Software Version: Company:
Protocol and Baud Rate: Network Address:
CONFIGURATION POINTS
POINT NAME BACnet Object RANGE DEFAULT ENTRY
SETPOINT
Occupied Heating Setpoint occupied_heat_setpoint 40-90 °F 70
Occupied Cooling Setpoint occupied_cool_setpoint 55-99 °F 76
Unoccupied Heating Setpoint unoccupied_heat_setpoint 40-90 °F 55
Unoccupied Cooling Setpoint unoccupied_cool_setpoint 45-99 °F 90
Effective Heat Setpoint effective_heat_setpoint 0-120 °F
Effective Cool Setpoint effective_cool_setpoint 0-120 °F
Optimal Start optm_start 0-4 hr 1
Optimal Start Type start_type 1=None
2=Temp Compensated
3=Learning Adaptive
Temperature Compensated
Heat Start K factor (min/deg) h_kfactor 0-99 15
Cool Start K factor (min/deg) c_kfactor 0-99 15
Occ Relative Humidity Setpoint occ_dehum_stpt 0-unocc setpoint %rh 60
Unocc Relative Humidity Setpoint unocc_dehum_stpt 30-100 %rh 95
DCV Max Ctrl Setpoint iaq_stpt_max 0-9999 ppm 650
Power Exhaust Setpoint
1
pexh_stpt 20-90 %Open 50
SPACE TEMPERATURE ALARM
Occupied Alarm Hysteresis occ_spt_alrm_hyst 0-20°F 5
Alarm Delay (min/deg) spt_alrm_delay 0-60 minutes 10
Unoccupied Low SPT Alarm Limit uno_spt_alrm_lo_lmt 35-90 °F 45
Unoccupied High SPT Alarm Limit uno_spt_alrm_hi_lmt 45-100 °F 95
SUPPLY TEMPERATURE ALARM
Low SAT Alarm Limit sat_lo_alrm_lim 15-90 °F 38
High SAT Alarm Limit sat_hi_alrm_lim 90-175 °F 160
SPACE HUMIDITY ALARM
Occupied High RH Alarm Limit (%RH) sprh_hi_alrm_lim 0-100%rh 70%rh
Alarm Delay (min/%RH) sprh_delay 0-30 min 5min
Unoccupied High RH Alarm Limit (%RH) unocc_sprh_lmt 0-100%rh 100%rh
Low RH Alarm Limit (%RH) sprh_lo_alrm_lim 0-100%rh 30%rh
IAQ / VENTILATION ALARM
Occupied High CO2 Alarm Limit (ppm) iaq_occ_hi_lmt 0-9999 ppm 1200