38
APPENDIX A -- USER INTERFACE MENUS (CON’T)
Field Assistant Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
OCCUPANCY (MAINTENANCE)
Properties>
Control Program Maintenance>
Occupancy
3 BAS On / Off keypad_ovrde 1=Inactive
2=Occupied
3=Unoccupied
Inactive
3 Pushbutton Override pb_status Off/Active
N/A Occupancy Contact occ_contact_status Off/On
3 Override Time Remaining ovrde_time 0-240 min
3 Schedules schedule Unoccupied/Occupied
RUNTIME (MAINTENANCE)
Properties>Control Program
Maintenance>Runtime
Supply Fan Runtime sfan_rntm xxxxx hr
Compressor 1 Runtime comp1_rntm xxxxx hr
Compressor 2 Runtime comp2_rntm xxxxx hr
Filter Runtime filter_rntm xxxxx hr
CURRENT PERFORMANCE DATA
Properties>Control Program>
Performance>Current
Performance Data
3, 2, 1 Equipment Runtime equip_rntm xxxxx hr
3, 2, 1 Economizer Utilization econ_util 0-100%
3, 2, 1 DCV Utilization dcy_util 0-100%
3, 2, 1 Unocc Free Cool Utilization ntfc_util 0-100%
3, 2, 1 Part Load Cooling Utilization partload_cool_util 0-100%
3, 2, 1 Full Load Cooling Utilization cool_util 0-100%
3, 2, 1 Heating Utilization heat_util 0-100%
3, 2, 1 Recorded High OAT rec_hi_oat -xxx - xxx_F
3, 2, 1 Recorded Low OAT rec_lo_oat -xxx - xxx_F
N/A Performance Data Collect/Reset
HISTORICAL PERFORMANCE DATA
Properties>Control Program>
Performance>Historical
Performance Data
Save Performance Daily save_perf_data Disable/Enable Disable
Equipment Runtime pre_equip_rntm xxxxx.x hr
Economizer Utilization pre_econ_util 0-100%
DCV Utilization pre_dcv_util 0-100%
Unocc Free Cool Utilization pre_ntfc_util 0-100%
Part Load Cooling Utilization pre_pl_cool_util 0-100%
Full Load Cooling Utilization pre_cool_util 0-100%
Heating Utilization pre_heat_util 0-100%
Recorded High OAT pre_hi_oat -xxx - xxx_F
Recorded Low OAT pre_lo_oat -xxx - xxx_F