
29
OAQ Sensor
This alarm indicates the mA input at the associated
channel falls below 3.5 mA or rises above 21 mA, or the
Network value for space RH is no longer being received.
Cooling, heating, and supply fan operation continues.
However, the controller’s IAQ control function uses
400ppm as the fixed outdoor air CO2 level until the fault
condition is corrected.
Space Temperature
When Occupied, a Space Temperature alarm is generated
if the space temperature falls below the lower limit or
rises above the upper limit.
When Unoccupied, an unoccupied space temperature
alarm is generated when the space temperature falls below
the alarm configuration Unoccupied Low SPT Alarm
Limit or when the space temperature rises above the alarm
configuration Unoccupied High SPT Alarm Limit.
The following values are related to the Space Temperature
alarm:
Alarming Temperature – This variable displays the value
of the space temperature that caused the alarm and is only
visible when the space temperature is in an alarm state.
Alarm Limit Exceeded – This variable displays the value
of the alarm setpoint that was exceeded by the alarming
space temperature and is only visible when the space
temperature is in an alarm state.
Supply Air Temperature
This alarm indicates the supply air temperature fell below
the alarm configuration Low SAT Alarm Limit or
exceeded the alarm configuration High SAT Alarm Limit
for 5 minutes. This alarm is inhibited until the RTU has
been running for 30 minutes to allow for system
stabilization after startup.
Setpoint Slider
This alarm indicates an open circuit is detected at the
setpoint adjustment input. This can only occur if the
Space Sensor Type is set to T56. Note that only an open
circuit results in an alarm. A short across this input offsets
the setpoints negatively by the amount configured by
configuration Setpoint Adjustment Range.
Switch Configuration
This occurs if more than one binary input (inputs 3, 5, 8,
and 9) is configured for the same function. When this
happens the two inputs (or more) configured wrong will
be disabled as an inputs. This alarm will automatically be
cleared when configuration is corrected.
An example of this would be: Input 3 = Compressor
Safety, input 5 = Fan Status, input 8 = Fan Status, and
input 9 = Humidistat; the alarm would be active, unit
would run, compressor safety and humidistat would
function normally, and Fan Status (inputs 5 & 8) will be
interpreted as “No Function.”
Analog Input Configuration
This occurs if more than one analog input (inputs 1 & 2)
is configured for the same sensor. When this happens the
two inputs will be disabled as inputs. This alarm will
automatically be cleared when configuration is corrected.
An example of this would be: Input 1 = IAQ Sensor, input
2 = IAQ Sensor; the alarm would be active, unit would
run, but the IAQ Sensor (inputs 1 & 2) will be interpreted
as “No Function.”
Space Relative Humidity
This alarm indicates the space humidity fell below the
alarm configuration Low Space Humidity Alarm Limit or
exceeded the alarm configuration High Space Humidity
Alarm Limit for 10 minutes. This alarm is inhibited until
the RTU runs for 15 minutes to allow for system
stabilization after startup.
Indoor Air Quality
This alarm indicates the space CO
2
level exceeds the
alarm configuration Occupied High CO
2
Alarm Limit for
1-minute. This alarm will be inhibited until the RTU has
been running for 2-minutes to allow for system
stabilization after startup.
Supply Fan Runtime
This alarm indicates the accumulated runtime exceeds the
unit configuration Supply Fan Service Alarm Timer value
(when not set to 0). This alarm is most commonly used to
indicate an equipment maintenance interval is due. The
supply fan runtime accumulator may be reset by setting
the maintenance point Reset Supply Fan Runtime Alarm
to Clear, and then back to Run – acknowledging each
selection by clicking the OK button when it appears.
Setting unit configuration Supply Fan Service Timer value
to 0 disables the supply fan runtime alarm function.
Compressor 1 Runtime
This alarm indicates the accumulated runtime exceeds the
unit configuration Compressor 1 Service Alarm Timer value
(when not set to 0). This alarm is most commonly used to
indicate an equipment maintenance interval is due. The
Compressor 1 Runtime accumulator may be reset by setting
the maintenance point Reset Comp 1 Runtime Alarm to
Clear, and then back to Run – acknowledging each selection
by clicking the OK button when it appears. Setting unit
configuration Compressor 1 Service Timer value to 0
disables the Compressor 1 Runtime alarm function.
Compressor 2 Runtime
This alarm indicates the accumulated runtime exceeds the
unit configuration Compressor 2 Service Alarm Timer value
(when not set to 0). This alarm is most commonly used to
indicate an equipment maintenance interval is due. The
Compressor 2 runtime accumulator may be reset by setting
the maintenance point Reset Comp 2 Runtime Alarm to
Clear, and then back to Run – acknowledging each selection
by clicking the OK button when it appears. Setting unit
configuration Compressor 2 Service Timer value to 0
disables the Compressor 2 runtime alarm function. Note that
this function is unavailable if the service configuration
Compressor Stages value is not set to Two Stages.
Filter
This alarm indicates the accumulated runtime exceeds the
unit configuration Filter Service Alarm Timer value
(when not set to 0). This alarm is most commonly used to
indicate a filter replacement is due. Reset the filter service
runtime accumulator by setting the maintenance point
Reset Filter Runtime Alarm to On, back to Off, and
clicking the OK button after each setting. Setting unit
configuration Filter Service Alarm Timer value to 0
disables the filter service alarm function.
TS---5580J---02
Comentarios a estos manuales