APPENDIX A -- USER INTERFACE MENUS (CON’T)
Field Assistant Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
ALARMS
Properties>
Contro l Program>
Alarm s
3, 2, 1 Safety Chain safety_alarm Normal/Alarm
3, 2, 1 Space Temperature Alarm Status spt_alrm_status Normal/Alarm
3, 2, 1 Space Temp Sensor spt_fail Normal/Alarm
3, 2, 1 Supply Air Temperature sat_alarm Normal/Alarm
3, 2, 1 Supply Air Temp Sensor loc_sat_sensor_fail Normal/Alarm
N/A Supply Fan Failure sfan_fail_alarm Normal/Alarm
3, 2, 1 Supply Fan in Hand sfan_hand_alarm Normal/Alarm
3, 2, 1 Indoor Air Quality iaq_alarm Normal/Alarm
3, 2, 1 Indoor Air Quality Sensor iaq_sensor_alarm Normal/Alarm
3, 2, 1 Space Relative Humidity sprh_hi_alarm Normal/Alarm
3, 2, 1 Space Relative Humidity Sensor sprh_sensor_fail Normal/Alarm
3, 2, 1 Filter filter_alarm Clean/Dirty
3, 2, 1 Local OAT Sensor loc_oat_sensor_fail Normal/Alarm
3, 2, 1 Economizer Operation econ_opr Normal/Alarm
3, 2, 1 Switch Configuration di_cfg_alarm Normal/Alarm
3, 2, 1 Analog Input Configuration ai_cfg_alarm Normal/Alarm
3, 2, 1 Supply Fan Runtime sfan_rntm_alarm Normal/Alarm
3, 2, 1 Compressor 1 Runtime comp1_rntm_alarm Normal/Alarm
3, 2, 1 Compressor 2 Runtime Comp2_rntm_alarm Normal/Alarm
3, 2, 1 Airside Linkage Alarm air_linkage_fail Normal/Alarm
TS---5580J---02