31
Heating Utilization
The value of the Heating Utilization when the current
performance data was last reset.
Previous High OAT
The value of the Recorded High OAT when the current
performance data was last reset.
Previous Low OAT
The value of the Recorded Low OAT when the current
performance data was last reset.
Third Party Networking
Third party communication and networking troubleshooting
should be done by or with assistance from the front end 3rd
party technician. A Module Status Report (Modstat) can be
run from Field Assistant (see Table 5 to perform). This lists
information about the board status and networking state. For
basic troubleshooting, see Table 6.
For further information about third party networking contact
Bryant applications engineering.
Table 5 – Manufacture Date
When troubleshooting, you may need to know a control module’s manufacture date.
Obtain the manufacture date from a... Notes
Module status report (modstat) To obtain a modstat with Field Assistant:
1. Press Function (FN) key and hold.
2. Then press period (.)
3. Release both buttons.
ThereportshowsthedateunderMain board hardware.
Sticker on the control board
“Serial No: OR2YMCxxxP ”
(Bar Coded & Typed Number)
The serial numbers are unique and contain embedded information, for example OR2420042P:
“OR2” --- These first three digits are unique to RTU Open and are used as an identifier.
“YM” --- These two digits identify the last digit of the year and month (in hex, A=10/Oct)
of manufacture. “42” would represent a date of manufacture of “Feb 2014”.
“C” --- T h o u s a n d s c o u n t e r 0 --- 9 a n d A --- Z ; A = 1 0 ; Z = 3 5
“xxx” --- These three digits represent the sequential number of units produced for a given
product for the mentioned manufacturing time period.
“P” --- This final digit represents the decade and toggles between “N” and “M” every
ten years.
Table 6 – Basic Protocol Troubleshooting
Problem Possible cause Corrective action
No communication with 3rd
party vendor
Incorrect settings on SW1, SW2 and SW3 Verify and correct switch settings. Cycle
powertoRTUOpenafterchangingswitch
settings.
RS485 Port has no voltage output
(check with RTU Open disconnected from RS485
communication bus):
•Bacnet
R
@ 9600/19.2K --- .01 to .045vdc
• Bacnet @ 38.4K --- .06 to .09vdc
• Bacnet @ 76.8K --- .1vdc
• Modbus @ 9600 --- 76.8K --- .124vdc
• N2 @ 9600 --- .124vdc
Verify RTU Open has correct power
supply.
Possible bad driver on board.
Check RS485 bus for external voltage
before reconnecting to the bus.
Verify devices are daisy chained and repeaters and bias
terminators are correctly installed.
Check 3rd party vendor RS485
communication wiring guidelines and
troubles hooting procedures.