APPENDIX B -- THIRD PARTY POINTS LIST
RTU Open Protocol Maps
Point Name
Point
Access
Units
BACnet Info Modbus Info N2 Info LonWorks Info
BACnet
Point Name
BACnet
Object ID
Modbus Register Type
Modbus
Register #
N2 Network
Point Type
N2 Network
Point
Address
SNVT Type SNVT Name
SPT Sensor Read Only °F
zone_temp_zone_temp
AI:1 Select.. Select.. Select
input_1 Read Only no units ai_1 AI:1001 Input Register (Float) 21 AI 2 Select
input_2 Read Only no units ai_2 AI:1002 Input Register (Float) 23 AI 3 Select
input_6 Read Only °F ai_6 AI:1006 Input Register (Float) 5 AI 7 Select
input_7 Read Only °F ai_7 AI:1007 Input Register (Float) 25 AI 4 Select
input_10 Read Only °F ai_10 AI:1010 Input Register (Float) 27 AI 5 Select
input_11 Read Only other ai_11 AI:1011 Input Register (Float) 29 AI 6 Select
slidepot voltage reading Read Only no units slidepot_volts AI:1012 Input Register (Float) 7 AI 8 Select
Active Compressor Stages Read Only no units comp_run AV:2020 Input Register (Float) 31 ADF 10 SNVT_count_inc(9) nvoCmpStages
Active Heat Stages Read Only no units heat_run AV:2003 Input Register (Float) 33 ADF 11 SNVT_count_inc(9) nvoHtStgs
Air Source Outdoor Air Temp Read Only °F link_ahu_oat AV:2609 Input Register (Float) 11 ADF 2 Select
Air Source Supply Air Temp Read Only °F link_sat AV:2608 Input Register (Float) 13 ADF 3 Select
Compressor 1 Runtime Read Only hr comp1_rntm AV:2017 Input Register (Float) 35 ADF 12 Select
Compressor 1 Service Alarm Timer R/W hr comp1_service_hrs AV:83006 Holding Register (Float) 37 ADF 13 Select
Compressor 2 Runtime Read Only hr comp2_rntm AV:2018 Input Register (Float) 39 ADF 14 Select
Compressor 2 Service Alarm Timer R/W hr comp2_service_hrs AV:83007 Holding Register (Float) 41 ADF 15 Select
Cooling Lockout Temperature R/W °F oat_cl_lockout AV:9002 Holding Register (Float) 43 ADF 16 SNVT_temp_p(105) nviClLckTemp
DCV Max Ctrl Setpoint R/W ppm iaq_stpt_max AV:3013 Holding Register (Float) 45 ADF 17 SNVT_ppm(29)
nviDCVMaxPPM
DCV Max Vent Damper Pos R/W %Open iaq_dpr_max AV:9011 Holding Register (Float) 47 ADF 18 SNVT_lev_percent(81) nviDCVMaxPos
Dehum Min VFD Output R/W % dehum_min_vfd AV:3028 Select.. Select.. Select
Economizer High OAT Lockout Temp R/W °F oat_ec_lockout AV:9008 Holding Register (Float) 49 ADF 19 Select
Economizer Output Read Only %Open econ_output AV:2022 Input Register (Float) 51 ADF 20 SNVT_lev_percent(81) nvoEconOut
Economizer Purge Min Pos R/W %Open econ_purge_min AV:9029 Holding Register (Float) 75 ADF 5 SNVT_lev_percent(81) nvoEcnPrgMin
Economizer Test R/W %Open econ_test AV:81001 Holding Register (Float) 53 ADF 21 Select
Effective Cool Setpoint Read Only °F eff_cl_stpt AV:3005 Input Register (Float) 55 ADF 22 SNVT_temp_p(105) nvoEffCoolSP
Effective Heat Setpoint Read Only °F eff_ht_stpt AV:3006 Input Register (Float) 57 ADF 23 SNVT_temp_p(105) nvoEffHeatSP
Factory Test Analog 1 Control R/W % ao1_fac_test AV:91001 Holding Register (Float) 59 ADF 24 Select
Factory Test Analog 2 Control R/W V ao2_fac_test AV:91002 Holding Register (Float) 61 ADF 25 Select
Fan Off Delay R/W seconds fan_delay_off AV:9024 Holding Register (Float) 63 ADF 26 Select
Filter Runtime Read Only hr filter_rntm AV:2015 Input Register (Float) 65 ADF 27 Select
Filter Service Alarm Timer R/W hr filter_service_hrs AV:2019 Holding Register (Float) 67 ADF 28 SNVT_count_inc(9) nviFltAlmTm
Heating Lockout Temperature R/W °F oat_ht_lockout AV:9003 Holding Register (Float) 69 ADF 29 SNVT_temp_p(105) nviHtLckTmp
HP Aux Heat Lockout Temp R/W °F oat_auxht_lockout AV:3025 Select.. Select.. Select
HP Rev Cycle Lockout Temp R/W °F hp_rev_cycle_lockout AV:9004 Holding Register (Float) 71 ADF 30 SNVT_temp_p(105) nviHPRvClLk
Indoor Air Quality CO2 (ppm) Read Only ppm iaq AV:1009 Input Register (Float) 73 ADF 31 SNVT_ppm(29) nvoIAQ
Linkage Max Damper Position Read Only % link_max_dmpr AV:2611 Input Register (Float) 77 ADF 6 Select
LowFanEconMinPos R/W %Open econ_min_2 AV:9030 Holding Register (Float) 89 ADF 32 SNVT_lev_percent(81) nviLwFnEcnMn
Max VFD Output R/W % max_vfd_spd AV:3026 Select.. Select.. Select
Maximum Heating SAT R/W °F sat_ht_max AV:83004 Holding Register (Float) 79 ADF 34 Select
Min VFD Output R/W % min_vfd_spd AV:3027 Select.. Select.. Select
Minimum Cooling SAT R/W °F sat_cl_min AV:83003 Holding Register (Float) 81 ADF 35 Select
Occ Relative Humidity Setpoint R/W %rh occ_dehum_stpt AV:3011 Holding Register (Float) 83 ADF 36 SNVT_lev_percent(81) nviOcRHSP
Optimal Start R/W hr optm_start AV:9026 Holding Register (Float) 147 ADF 61 SNVT_count_inc(9) nviOptmStart
Outdoor Air Quality CO2 (ppm) Read Only ppm oaq AV:1012 Input Register (Float) 85 ADF 37 SNVT_ppm(29) nvoOAQ
Outdoor Air Temperature Read Only °F oa_temp AV:1003 Input Register (Float) 87 ADF 38 SNVT_temp_p(105) nvoOAT
Override Time Remaining Read Only min ovrde_time AV:2016 Input Register (Float) 93 ADF 41 SNVT_count_inc(9) nvoOvrTmRem
Password Protected Output Variable R/W no units ppo AV:90000 Holding Register (Float) 95 ADF 42 Select
Power Exhaust Setpoint R/W %Open pexh_stpt AV:3010 Holding Register (Float) 97 ADF 43 SNVT_lev_percent(81) nviPwrExhSP
Power Fail Restart Delay R/W seconds start_delay AV:9007 Holding Register (Float) 127 ADF 58 SNVT_count_inc(9) nviUntStrDly
Setpoint R/W °F occ_cl_stpt AV:3001 Holding Register (Float) 9 ADF 4 SNVT_temp_p(105) nviOccCoolSP
Setpoint R/W °F occ_ht_stpt AV:3002 Holding Register (Float) 19 ADF 9 SNVT_temp_p(105) nviOccHeatSP
Setpoint R/W °F unocc_cl_stpt AV:3003 Holding Register (Float) 15 ADF 7 SNVT_temp_p(105) nviUnoccClSP
Setpoint R/W °F unocc_ht_stpt AV:3004 Holding Register (Float) 17 ADF 8 SNVT_temp_p(105) nviUnoccHtSP
Setpoint Adjustment Read Only °F stpt_adj AV:1006 Input Register (Float) 99 ADF 44 SNVT_temp_p(105) nvoSPAdjust
Setpoint Adjustment Range R/W °^F stpt_adj_range AV:9015 Holding Register (Float) 101 ADF 45 SNVT_count_inc(9) nviSPAdjRng
Space Relative Humidity Read Only %rh space_rh AV:1011 Input Register (Float) 103 ADF 46 SNVT_lev_percent(81) nvoSpaceRH
Space Temperature - Prime Variable Read Only °F space_temp AV:2007 Input Register (Float) 107 ADF 48 SNVT_temp_p(105) nvoSpaceTemp
Space Temperature Offset Pot Read Only °F stpt_adj_offset AV:91006 Input Register (Float) 105 ADF 47 Select